Options

86

MultiPort 4 Card

The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of

alarm conditions UPS operation On Battery and Low Battery condition. A typical application is to

allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power

failure-low battery) of a single UPS.
This card is supported in any of the three Liebert IntelliSlot bays on the Liebert NX.

Figure 57 MultiPort 4 card pin assignment

UPS

CPU

CPU

CPU

CPU

Pin

Assignment

Description

1

Low Battery

2

Not Used

3

Not Used

4

Not Used

5

Not Used

6

Not Used

7

Low Battery Common

8

Utility Fail Common

9

Utility Fail