Liebert NX Operating Modes

The Liebert NX can operate in any of four modes, as shown in Table 20. This section provides

instructions on switching between modes, resetting the UPS, switching the inverter On and Off and

performing other operations.
Table 20

UPS operating modes

Operating Mode

Circuit Breaker

State

Description

Normal

Operation

CB1:ON

CB2:ON

CB3:OFF

CB5:ON

The UPS is powering the load.

On Maintenance

Bypass

CB1:OFF

CB2:OFF

CB3:ON

CB5:OFF

The UPS is shut down but the load is connected to utility power via the

Maintenance Bypass Supply line.

NOTE: The load is not protected against disturbances in AC input power in

this mode.

On Test

CB1:ON

CB2:ON

CB3:ON

CB5:OFF

No load power is supplied by the UPS. The load is connected to utility power

via the Maintenance Bypass Supply line.

NOTE: The load is not protected against disturbances in AC input power in

this mode.

On Static Bypass

CB1:ON or OFF

CB2:ON

CB3:OFF

CB5:ON

The load power is supplied through the static bypass line. This may be

considered as a temporary mode during load transfers between inverter and

maintenance bypass or supply under abnormal operating conditions.

NOTE
1. The user controls and indicators mentioned in these procedures are identified in 8.0 -

Operator Control and Display Panel.

2. The audible alarm may sound at various points during these procedures. It can be canceled

at any time by pressing the SILENCE ON/OFF push button.

NOTE
This section refers to some modes and conditions that are set or adjusted using proprietary

service software. To take advantage of all the available features for the Liebert NX, the unit

must be commissioned by a Liebert factory-trained service engineer.