UPS Status Messages

94

Bypass Unable to Trace

This alarm is triggered by an inverter software routine when the amplitude or frequency of

bypass voltage is beyond the normal range.

The amplitude threshold is fixed for positive and negative 10% rating.

This alarm automatically resets once the bypass voltage goes normal.

First verify that the bypass voltage and frequency displayed on the panel is within the selected

range. Note here the rated voltage and frequency are specified by “Output voltage level” and

“Output frequency level” respectively.

If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency

presented to the UPS. Check the external supply if it is found to be faulty.

Contact Liebert Global Services at 800-543-2378 for assistance.

Bypass Abnormal

This alarm is triggered by an inverter software routine when the amplitude or frequency of

bypass voltage exceeds the limit.

This alarm automatically resets once the bypass voltage goes normal.

First check whether there are relevant alarms such as “Bypass disconnect open,” “Bypass

phase reverse” and “Mains neutral lost.” If they appear, solve them first.

Then verify that the bypass voltage and frequency displayed on the panel is within the bypass

limit. Note here the rated voltage and frequency are specified by “Output voltage level” and

“Output frequency level” respectively.

If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency

presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is

likely to trigger this alarm frequently, the bypass limit can be increased through the configuration

software according to the customer’s agreement.

Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter Asynchronous

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the

condition clears.

First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first.

Verify the waveform of the bypass voltage.

Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter Fault

This alarm indicates a fault condition exists within the inverter.

Contact Liebert Global Services at 800-543-2378 for assistance.

Output Voltage Abnormal

This alarm indicates the inverter voltage waveform is abnormal.

Contact Liebert Global Services at 800-543-2378 for assistance.

Input Current Abnormal

This alarm indicates the rectifier input current is abnormal.

Contact Liebert Global Services at 800-543-2378 for assistance.

Inv. Inductor Overtemp.

The temperature of the inverter filter inductor or inverter common mode inductor is too high to

keep inverter running.

This alarm is triggered by the signal from a thermostat mounted in the inverter filter inductor.

The UPS would recover automatically after a 5 minute delay from the disappearance of the

overtemperature signal.

If the overtemperature condition is true then check for and verify:

High ambient air temperature.

Blocked cooling airway

Any fan failure

Prolonged inverter overload.

Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter Overtemp.

The temperature of the inverter heat sink is too high to keep inverter running.

This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter

bridge heat sink.

The UPS will recover automatically after a 5 minute delay from the disappearance of the

overtemperature signal.

If the overtemperature condition is true then check for and verify:

high ambient air temperature.

blocked cooling airway.

any fan failure.

prolonged inverter overload.

Contact Liebert Global Services at 800-543-2378 for assistance.

Fan Fault

At least one of the cooling fans has failed. Contact Liebert Global Services at 800-543-2378 for

assistance.

Table 36

UPS status messages

Event Message

Description / Suggested Action (if any)