4 ups electrical characteristics, Table 8 ups terminal, Ups electrical characteristics – Emerson Liebert NX 480V User Manual
Page 42: Table 8, Ups terminal, Table 8 , with respect, Table 8 , with respect to, To table 8, Ee table 8, 4 - ups elec
UPS Specifications
34
5.4
UPS Electrical Characteristics
Table 8
UPS terminal
Input (For Single-Input Unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole;
40
48
66.8
80.2
90
8M 54106
ADR21
60
72
100.2
120.3
125
8M 54108
ADR21
80
96
133.6
160.4
175
8M 54157
ADR21
100
120
167.1
200.5
225
8M
54167
ADR50
120
144
200.5
240.6
250
8M 54172-TB
ADR50
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40
48
67.5
83
90
8M 54106
ADR21
60
72
101.3
124.5
125
8M 54108
ADR21
80
96
135
166
175
8M 54157
ADR21
100
120
168.8
207.6
225
8M
54167
ADR50
120
144
202.5
249.1
250
8M 54172-TB
ADR50
Bypass input (for dual input units)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40
48
66.8
70
8M 54106
ADR21
60
72
100.2
110
8M 54107
ADR21
80
96
133.6
150
8M 54152-TB
ADR21
100
120
167.1
175
8M
54157
ADR21
120
144
200.5
225
8M 54167
ADR50
Output
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40
48
66.8
70
8M 54106
ADR21
60
72
100.2
110
8M 54107
ADR21
80
96
133.6
150
8M 54152-TB
ADR21
100
120
167.1
175
8M
54157
ADR21
120
144
200.5
225
8M 54167
ADR50