Operator Control and Display Panel
59
8.3
Control Buttons
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the
inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 42. The
function of each button is described in Table 16.
Figure 42 Location of control buttons
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.
Table 16
Control buttons
Button
(see Figure 42)
Function
EPO
Completely shuts down the UPS, including the static switch.
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button
completely shuts down the unit and cuts off power to the critical load.
Inverter Off
Press this button to shut down the inverter during operation. The load will be transferred to
static bypass.
Fault Clear
After the UPS shuts down due to a fault and the alarm condition has been resolved, press
this button to clear the fault and restart the UPS.
Silence On/Off
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will
sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.
Inverter On
Press this button to start the inverter and transfer from static bypass to inverter.
NOTE: If the inverter is not ready, this will not activate the UPS.
Silence On/Off button
INVER TER ON
SILENC E ON/ OFF
INVER TER OFF
FAULT C LEAR
EPO
LED1
LED2
LED3
LED4
LED5
STATUS
F2
F4
HELP
F1
F3
?
L-N current (A)
Frequency (HZ)
L-L voltage (V )
P owerFactor
L1-N/L 2
71. 4
59. 9
480
0. 99
L 2-N/ L3
70.8
59.9
480
0. 99
L 3-N/ L1
71.3
59.9
480
0.99
Output
Input disconnect closed
01-06 09:15
Bypass abnormal
01-06 09 :15
Liebert NX
2007-01-06
09:20:37
S ingle
Normal
80kV A-3X 3
Output disconnect closed
01-06 09:15
Bypass
Main
Button cover
EPO button
Inverter On button
Inverter Off button
Fault Clear button