Operator Control and Display Panel

59

8.3

Control Buttons

The Control Buttons on the front panel may be used to shut down the UPS completely, turn the

inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 42. The

function of each button is described in Table 16.

Figure 42 Location of control buttons

NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.

Table 16

Control buttons

Button

(see Figure 42)

Function

EPO

Completely shuts down the UPS, including the static switch.

CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button

completely shuts down the unit and cuts off power to the critical load.

Inverter Off

Press this button to shut down the inverter during operation. The load will be transferred to

static bypass.

Fault Clear

After the UPS shuts down due to a fault and the alarm condition has been resolved, press

this button to clear the fault and restart the UPS.

Silence On/Off

Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will

sound the buzzer again.

If the alarm buzzer is not beeping, press this button to test the alarm sound.

Inverter On

Press this button to start the inverter and transfer from static bypass to inverter.

NOTE: If the inverter is not ready, this will not activate the UPS.

Silence On/Off button

INVER TER ON

SILENC E ON/ OFF

INVER TER OFF

FAULT C LEAR

EPO

LED1

LED2

LED3

LED4

LED5

STATUS

F2

F4

HELP

F1

F3

?

L-N current (A)

Frequency (HZ)
L-L voltage (V )
P owerFactor

L1-N/L 2

71. 4
59. 9

480

0. 99

L 2-N/ L3

70.8

59.9
480

0. 99

L 3-N/ L1

71.3
59.9
480

0.99

Output

Input disconnect closed

01-06 09:15

Bypass abnormal

01-06 09 :15

Liebert NX

2007-01-06

09:20:37

S ingle

Normal

80kV A-3X 3

Output disconnect closed

01-06 09:15

Bypass

Main

Button cover
EPO button

Inverter On button

Inverter Off button

Fault Clear button