Installation Drawings
50
Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX
FRONT
(Without Covers
REAR
(Without Covers
FRONT
(With Door Open)
E1-E4, F
B1-B4
A
D
B1-B4
E1-E4
C1-C4
G1-G4,
H1-H4
G1-G4,
H1-H4
C1-C4
Run
From
To
Conductors
A
Utility Source
Parallel Cabinet
Ph A, B, C - System Input
B1-B4
Parallel Cabinet
UPS #1-UPS #4 Module
AC Input
Ph A, B, C - UPS Inputs
C1-C4
UPS #1-UPS #4 Module
AC Output
Parallel Cabinet
Ph A, B, C - UPS Outputs
D
Parallel Cabinet
Critical Loads
Ph A, B, C - System Outputs
E1-E4
Parallel Cabinet
UPS #1-UPS #4 Module
Gnd
Ground - UPS
F
Parallel Cabinet
Building Gnd
Ground - System
G1-G4
Parallel Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
Output Breaker Aux Contact
H1-H4
Parallel Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
UPS Bypass Detection