Installation Drawings

50

Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX

FRONT

(Without Covers

REAR

(Without Covers

FRONT

(With Door Open)

E1-E4, F

B1-B4

A

D

B1-B4

E1-E4

C1-C4

G1-G4,
H1-H4

G1-G4,
H1-H4

C1-C4

Run

From

To

Conductors

A

Utility Source

Parallel Cabinet

Ph A, B, C - System Input

B1-B4

Parallel Cabinet

UPS #1-UPS #4 Module

AC Input

Ph A, B, C - UPS Inputs

C1-C4

UPS #1-UPS #4 Module

AC Output

Parallel Cabinet

Ph A, B, C - UPS Outputs

D

Parallel Cabinet

Critical Loads

Ph A, B, C - System Outputs

E1-E4

Parallel Cabinet

UPS #1-UPS #4 Module

Gnd

Ground - UPS

F

Parallel Cabinet

Building Gnd

Ground - System

G1-G4

Parallel Cabinet

UPS #1-UPS #4 Module

UPS Parallel Logic Board (M3)

Output Breaker Aux Contact

H1-H4

Parallel Cabinet

UPS #1-UPS #4 Module

UPS Parallel Logic Board (M3)

UPS Bypass Detection