UPS Status Messages

97

Battery Float Charging

Battery is float charging

Battery Boost Charging

Battery is boost charging

Battery Discharging

Battery is discharging

Battery Period Testing

Battery is period self-testing.

Batt. Capacity Testing

Battery is capacity self-testing.

Batt. Maint. Testing

Battery is maintenance self-testing.

UPS System Testing

UPS System is testing

Inverter in Setting

Inverter is in parameter setting

Rectifier in Setting

Rectifier is in parameter setting

Balancer Fault

Internal VDC (+) and VDC (-) offset by over 50V exceeding the inverter DC offset compensation

capacity. Inverter shuts down. Load transfers to bypass.

Operation Invalid

This record is registered following an incorrect operation.

Byp. Abnormal Shutdown

Both bypass and inverter voltages unavailable. Load interruption

Setting Save Error

History records not saved (Reserved)

Protocol version clash

Firmware incompatibility between monitor board and digital signal processor board

MBP-T cabinet Fan Fault

Maintenance bypass cabinet fans fault

Ext Input TX Overtemp

External input isolation transformer overtemperature

Ext Output TX Overtemp

External output isolation transformer overtemperature

Battery Room Alarm

Environment in Battery Room Needs Attention

Rec Flash Update

Rectifier firmware is being updated

Inv Flash Update

Inverter firmware is being updated

Monitor Flash Update

Monitor firmware is being updated

Input contactor fault

Input contactor fault

LBS abnormal

LBS is abnormal

DSP firmware error

The inverter firmware is not compatible with the rectifier firmware.

Fan power fail

Fan power has failed

Keyboard fault

Keyboard has a fault. Check the cable between keyboard with U2 board. Contact Liebert Global

Services at 800-543-2378 for assistance.

KVA Invalid

An invalid kVA has been configured in unit.Contact Liebert Global Services at 800-543-2378 for

assistance.

KVA updated

The capacity updating is successful.

Output ground fault

Output Line is shorted with ground

Table 36

UPS status messages

Event Message

Description / Suggested Action (if any)