Installation Drawings

37

6.0

I

NSTALLATION

D

RAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert

NX UPS System cabinets.

Figure 21 Dimensional view- front and left side views

39.6mm

(1.6")

997mm

(39.3")

360mm

(14.2")

Center of Gravity
Without Internal Battery

Left Side

2000 mm

(78.7")

Front

600 mm

(23.6")

301mm

(11.9")

Liquid

Crystal

Display

1. All dimensions are in millimeters (in.).
2. Eight-inch minimum clearance above unit

required for air exhaust.

3. Keep cabinet within 15 deg. of vertical while

handling.

4. Top and bottom cable entry available through

removable access plates. Remove access plate,

punch to suit conduit size and replace.

5. Color - black.
6. Unit bottom is structurally adequate for

forklift handling.

7. Open door to replace air filter, washable type.
8. M10 threaded mounting holes used for

seismic anchoring or floor stand.
NOTE: If floor stand is used, the weight of the

unit must be supported under all casters.

9. Each mounting location is supported by (2)

10ga. (.135") galvanized steel. The threaded

insert is approx. 3/4" deep. Mounting holes

are underneath unit base; mounting bolts

must be threaded into unit.

10. Includes side panel. Side panels must be

removed from adjacent units that are bolted

together.

11. Leveling feet are not designed to carry the full

weight of the cabinet.

12. Finger-tighten leveler against the floor, then

tighten with a wrench less than 2 turns for

friction fit against floor.