UPS Status Messages

96

DC Bus Overvoltage

Rectifier, inverter and battery converter were shut down because DC bus voltage is too high.

Check whether there is a fault in rectifier side. If not, check whether overload occurs.

Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Global

Services at 800-543-2378 for assistance.

Parallel Connect Fault

The parallel cables are not connected correctly in a parallel system.

Reset the fault by pressing the Fault Clear button, then restart the inverter by pressing the

Inverter On button.

If the UPS does not resume normal operation, contact Liebert Global Services at

800-543-2378 for assistance.

Bypass Overcurrent

Bypass current is over limit above 135% rating. The UPS just alarms and does nothing. Refer to

your installation documentation or contact Liebert Global Services at 800-543-2378 for

assistance.

LBS Active

The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus

configuration.

Battery ground fault

Battery ground fault from dry contact signal. Contact Liebert Global Services at 800-543-2378

for assistance.

Inverter turned On

manually

Manual Turn On via front panel

Inverter turned Off

manually

Manual Turn Off via front panel

EPO

Emergency Power Off

Transfer Confirm

Interrupted Transfer Confirm

Transfer Cancel

Interrupted Transfer is cancel

Unit Off Confirm

Unit Turned Off Confirm

System Off Confirm

Parallel System Turned Off Confirm

Fault Reset

Fault Reset

Alarm Silence

Alarm Silence

Turn On Fail

Turn On Fail

Alarm Reset

Audible Alarm Reset

Bypass Mode

UPS in Bypass Mode

Normal Mode

UPS in Normal Mode

Battery Mode

UPS in Battery Mode

Check UPS output

UPS Shutdown, output power-down

Output Disabled

UPS Output Disabled

Generator Connected

Generator is connected and a signal is sent to UPS

Input CB Open

Input CB is Open

Input CB Closed

Input CB is Closed

Bypass CB Open

Bypass CB is Open

Bypass CB Closed

Bypass CB is Closed

Output CB Open

Output CB is Open

Output CB Closed

Output CB is Closed

Maint. CB Open

Maintenance CB is Open

Maint. CB Closed

Maintenance CB is Closed

Battery Reverse

Connect the battery again and check the wiring of batteries

No Battery

Check the battery and the wiring of batteries

Auto start

After the UPS was shut down at end of discharge, inverter auto starts when utility is restored

BCB closed

BCB closed from dry contact signal

BCB open

BCB open from dry contact signal

Table 36

UPS status messages

Event Message

Description / Suggested Action (if any)