Electrical Connections

17

2.3.1 Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 7

Input dry contacts

2.3.2 Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 1

Input dry contacts at X3

Position

Name

Description

J4.1

ENV

3

Battery Room Alarm (N.C.)

J4.2

BtG

Battery Ground Fault Detection (N.C.)

J4.3

GEN

1,2

Generator Join Detection (N.O.)

J4.4

+12V

+12V Power

1 - Must be configured using configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.

Table 2

Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT

1

Input transformer over temperature (N.C.)

J26.2

AUX_I

Reserved

J26.3

+12V

+12V Power

J26.4

GND

Power Ground

J30.1

FUSE

Reserved

J30.2

F_FAN

Fan Fail Alarm (N.C.)

J30.3

T_OT

1

Output Transformer Overtemperature (N.C.)

J30.4

AUX_O

Reserved

1

- Must be configured using configuration software before becoming active.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded

for maximum runs between 82 and 197 feet (25-60m), respectively.

+1

2V

GE

N

Bt

G

EN

V

GN

D

GN

D

+1

2V

AU

X

_I

T_

IT

AU

X

_0

T_

0T

F_

F

A

N

FU

S

E

OL

FB

DR

V

+12V

+12V

+12V

+12V

X3

J4

J26

J30

J10

NOTE: The black square () on each slot indicates Pin 1.