beautypg.com

Operation, 3 battery temperature sensor operation – Magnum Energy MS-AEJ Series User Manual

Page 37

background image

Page 31

© 2007 Magnum Energy Inc.

-0.75

-0.6

-0.45

-0.3

-0.15

0

0.15

0.3

0.45

0.6

0.75

0

5

1 0

1 5

2 0

2 5

3 0

3 5

4 0

4 5

5 0

Tem perature reading from BTS (in degrees )

T em p eratu re C o m p en satio n u sin g B T S

0C

32F

5C

41F

10C

50F

45C

113F

30C

86F

40C

104F

35C

95F

25C

77F

20C

68F

15C

59F

50C

122F

48V D C units

+3 .0V
+2 .4V
+1 .8V
+1 .2V
+0 .6V

N o C hange

-0.6V
-1.2V
-1.8V
-2.4V
-3.0V

C

ha

ng

e t

o

ba

tter

y c

h

ar

g

ing

v

o

ltag

e

no B TS

c onnec ted

24 V D C units

+1.5 V
+1.2 V
+0.9 V
+0.6 V
+0.3 V

N o C hange

-0 .3V
-0 .6V
-0 .9V
-1 .2V
-1 .5V

Figure 3-4, BTS Temperature to Charge Voltage Change

3.2.2 Transfer Time
While in the Standby Mode, the AC input is continually monitored. Whenever AC power falls below

the VAC dropout voltage (80 VAC per leg, default setting), the inverter automatically transfers back

to the Invert Mode with minimum interruption to your appliances - as long as the inverter is turned

on. The transfer from Standby mode to Inverter mode occurs in approximately 16 milliseconds.

While the MS-AE Series is not designed as a computer UPS system, this transfer time is usually

fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the

loads to transfer without resetting. The lower this setting, the longer the effective transfer will be

and therefore, the higher the probability for the output loads to reset. This occurs because the

incoming AC voltage is allowed to fall to a level that is so low, that when the transfer does occur

(in addition to the relay transfer time) the voltage on the inverters output has already fallen low

enough level to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators

with an unstable output) may nuisance transfer. This commonly happens when powering loads

that are larger than the generator can handle - causing the generator’s output to constantly fall

below the inverters input VAC dropout threshold.

Info: When switching from Inverter Mode to the Standby Mode, the inverter waits approxi-

mately 15 seconds to ensure the AC source is stable before transferring.

3.3 Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the battery temperature around

the batteries, this information allows the multistage battery charger to automatically adjust the

battery charge voltages for optimum charging performance and longer battery life.
When the BTS is installed, the charge voltage while in the Bulk, Absorb or Float charge mode will

either increase or decrease if the battery temperature is greater or lower than 77°F (25°C). If the

temperature around the BTS is below 77°F (25°C) the charge voltage increases and if the tem-

perature around the BTS is higher than 77°F (25°C), the charge voltage decreases. The further

the temperature change from 77°F (25°C), the greater the change in the charging voltage. See

fi gure 3-4 to determine how much the charge voltage changes (increases or decreases) depend-

ing on the temperature reading of the BTS. For example, the nominal Absorb charge voltage for a

fl ooded battery at 77°F (25°C) on a 24-volt model is 29.2VDC. If the battery temperature is 95°F

(35°C), the Absorb charge voltage would decrease to 28.6VDC (29.2 nominal - 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be compensated and

charges at a temperature of 77°F (25°C). Without the BTS installed, the life of the batteries may

be reduced if they are subjected to large temperature changes.

Info: The temperature to voltage compensation slope the BTS uses is 5mV/°C/Cell from

0-50°C.

Operation