beautypg.com

Installation – Magnum Energy MS-AEJ Series User Manual

Page 20

background image

© 2007 Magnum Energy Inc

Page 14

Method 2 (see fi gure 2-6): When the AC and DC service panels are near each other, then the AC

Grounding Electrode Conductor (GEC – AC) and DC Grounding Electrode Conductor (GEC – DC)

can be connected to a single Grounding Electrode. In this method - since there are multiple

connections to the DC Grounding Electrode (GEC – DC) - the size of the DC Grounding Electrode

Conductor can not be smaller than the largest conductor in the DC system (usually the battery-

to-inverter cable).

Figure 2-6, Multiple Connections to DC Ground Rod (Method 2)

Figure 2-7, Single Connection to DC Ground Rod (Method 3)

Method 3 (see fi gure 2-7): The AC Grounding Electrode Conductor (GEC – AC) is bonded to the

DC ground point and the DC Grounding Electrode Conductor (GEC – DC) is the only connection to

the Grounding Electrode, which must be a rod, pipe, or plate electrode.
In this method, since there is only one connection to the ground rod, the DC Grounding Electrode

Conductor is not required to be larger than #6 AWG (13 mm

2

) copper. The reasoning for allowing

this smaller grounding electrode conductor is that it is only required to stabilize the system volt-

age with respect to earth and the other properly-sized conductors in each electrical system will

safely carry any fault currents if they occur.

Installation

A C

D C S e rvice

P a n e l

A C S e rvice

P a n e l

D C E lec tric al S y s tem

A C E lec tric al S y s tem

N eutral

Positive

N egative

D C

G rounding

S y s tem

N e g a tive

S B J

GC

GE

GE C -A C

E GC - A C

AC Ground

D C Ground

S B J

E GC - D C

GC

N e u tra l

H ot

GE C -D C

GB B

GB B

Grounding Electrode

(AC and D C sides shared)

M S -A E S e rie s In ve rte r/C h a rg e r

A C

D C S e rvice

P a n e l

A C S e rvice

P a n e l

D C E lec tric al S y s tem

A C E lec tric al S y s tem

N eutral

Positive

N egative

D C

G rounding

S y s tem

N e g a tive

S B J

GC

GE C -A C

E GC - A C

AC Ground

D C Ground

S B J

E GC - D C

GC

N e u tra l

H ot

GE C -D C

GE

GB B

GB B

Grounding Electrode

(D C side dedicated)

M S -A E S e rie s In ve rte r/C h a rg e r