Magnum Energy MS-AEJ Series User Manual
Page 21

Page 15
© 2007 Magnum Energy Inc.
2.2.2 System Bonding Jumper
The MS-AE Series inverter does not include an internal bond between the Grounded Conductor
(AC neutral/DC negative) and the equipment grounding terminals. This bond [System Bonding
Jumper (SBJ)] is usually done in the main distribution panel for each electrical system.
CAUTION: There should be one and only one point in each electrical system (both AC and
DC) where the Grounded Conductor is attached to the Grounding Electrode Conductor.
AC Side – The size of the System Bonding Jumper (SBJ) in the AC electrical system is based on
the area of the largest AC ungrounded conductor. In accordance with the NEC, use Table 2-1 to
determine the System Bonding Jumper size compared to the largest AC ungrounded conductor.
DC Side - The size of the System Bonding Jumper (SBJ) in the DC electrical system must not be
smaller than the DC Grounding Electrode Conductor (GEC – DC) used, which is determined from
the grounding method that will be used (see section 2.6.1).
2.2.3 Equipment Grounding Conductor
The inverter case and all other non-current-carrying exposed metal surfaces in the entire elec-
trical system that may be accidentally energized must be grounded. The equipment-grounding
conductor must be sized to safely carry the maximum ground-fault current likely to be imposed
on it from where a ground-fault may occur. In accordance with the NEC, use Table 2-2 to size the
equipment-grounding conductors. This table requires that the equipment-grounding conductor
be sized according to the rating of the overcurrent device protecting the circuit.
CAUTION: The connections and wiring for the equipment-grounding conductor must be
continuous to allow fault currents to properly operate overcurrent devices. Where equip-
ment is removed and this disconnects the bonding connection between the grounding
electrode conductor and exposed conducting surfaces, a bonding jumper must be installed
while the equipment is removed.
AC Side - Where the AC output from the inverter is connected to an AC load center, there should
be an equipment grounding conductor connected between the inverter case and the grounding
point in the AC load center. The AC Equipment Grounding Conductor (EGC – AC) is sized per Table
2-2 and is connected to the inverter’s AC equipment grounding terminal shown in fi gure 2-12.
DC Side - Since the currents on the DC side are higher than the AC side (5 times at 24 volts, 2.5
times at 48 volts), the equipment grounding needs are different. The DC Equipment Grounding
Conductor (EGC – DC) is sized per Table 2-2 and connected to the DC equipment grounding terminal
on the inverter shown in fi gure 1-2 (item 12).
Table 2-2, Equipment Grounding Conductor Sizing
Rating of Overcurrent
Device
Minimum Size of
Copper Ground Wire
15 amp
#14 AWG
20 amp
#12 AWG
30 - 60 amp
#10 AWG
100 amp
#8 AWG
200 amp
#6 AWG
300 amp
#4 AWG
400 amp
#3 AWG
Equipment Grounding Conductor Sizing
Installation