Installation, 2 grounding inverters – Magnum Energy MS-AEJ Series User Manual
Page 18

© 2007 Magnum Energy Inc
Page 12
Figure 2-4, Grounding System for MS-AE Series
2.2 Grounding Inverters
The inverter/charger should always be connected to a permanent, grounded wiring system. An
inverter system that is properly grounded will limit the risk of electrical shock, reduce radio fre-
quency noise from the inverter and minimize excessive surge voltages induced by lightning. This is
done by ensuring there is a well-defi ned, very low-resistance path from the electrical system to the
grounding system. This low-resistance path helps stabilizes the electrical system voltage with re-
spect to ground and carries fault currents directly to ground if the electrical system malfunctions.
To understand how the conductors in the electrical circuit will be connected to the system ground,
the following terms should be understood:
Grounded Conductor (GC): The wire/cable in the electrical system that normally carries current
(usually the AC neutral and/or the DC negative); and is intentionally connected or “bonded” to
the ground system. This wire or the ends of this wire should be colored white or gray.
Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current and
is used to connect the exposed metal parts of equipment - that might be accidentally energized
- to the grounding electrode system or the grounded conductor. This wire or the ends of this
wire should be green or green with a yellow stripe; or this wire can be bare copper.
Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry current and
connects the grounded conductor and/or the equipment grounding conductor to the grounding
electrode at the service equipment.
Grounding Electrode (GE): A ground rod or conducting element that establishes an electrical
connection to the earth.
System bonding jumper (SBJ) The connection between the grounded circuit conductor in the
electrical system and the equipment grounding conductor at a separately derived system.
The MS-AE Series inverter/charger uses both AC and DC power; however the AC electrical system
is isolated from the DC electrical system by an internal transformer. Although this inverter/charger
has two electrical systems, each electrical system must be properly grounded and connected to
a common “earth” reference; refer to fi gure 2-4.
For proper grounding, each electrical system must connect all exposed metal parts of equipment
(via Equipment Grounding Conductors - EGC) and one of the current-carrying conductors (Grounded
Conductor - GC) together at a common point (Ground Bus-Bar - GBB) usually by a System Bonding
Jumper (SBJ) in an electrical service disconnect panel. The common point of each electrical system
is then connected (via Grounding Electrode Conductor - GEC) to the common ground reference,
such as a ground rod (Grounding Electrode - GE). This connection to earth should only be made
at one point in each electrical system; otherwise, parallel paths will exist for the currents to fl ow.
These parallel current paths would represent a safety hazard and are not allowed in installations
wired per the NEC/CEC.
•
•
•
•
•
A C
D C S e rvice
P a n e l
A C S e rvice
P a n e l
D C E lec tric al S y s tem
A C E lec tric al S y s tem
N eutral
Positive
N egative
D C
G rounding
S y s tem
N e g a tive
S B J
GC
GE
GE C -A C
E GC
AC Ground
D C Ground
S B J
E GC
GC
N e u tra l
H ot
GE C -D C
GE
GE
GB B
GB B
Grounding Electrode
(AC and D C sides shared)
Grounding Electrode
(D C side dedicated)
Grounding Electrode
(AC side dedicated )
or
or
M S -A E S e rie s In ve rte r/C h a rg e r
Installation