beautypg.com

Installation – Magnum Energy MS-AEJ Series User Manual

Page 24

background image

© 2007 Magnum Energy Inc

Page 18

2.3.1 DC Wire Sizing
It is important to use the correct DC wire to achieve maximum effi ciency from the system and

reduce fi re hazards associated with overheating. Always keep your wire runs as short as practical

to help prevent low voltage shutdowns and keep the DC breaker from nuisance tripping (or open

fuses) because of increased current draw. See Table 2-3 to select the minimum DC wire size (and

corresponding overcurrent device) required based on your inverter model. The cable sizes listed

in Table 2-3 for your inverter model are required to reduce stress on the inverter, minimize voltage

drops, increase system effi ciency and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery bank is greater than 5 feet, the DC wire will need

to be increased. Longer distances cause an increase in resistance, which affects the performance

of the inverter. Continue to use the overcurrent device previously determined from Table 2-3

and then refer to Table 2-4 to determine the minimum DC wire size needed for various distances

based on your inverter model.
2.3.2 DC Overcurrent Protection

For safety and to comply with electrical code regulations, you must install a DC overcurrent pro-

tection device in the positive DC cable line to protect your DC cables. This DC overcurrent device

can be a fuse

or circuit breaker and

must be DC rated. It must be correctly sized according to

the size of DC cables being used, which means it is required to open before the cable reaches its

maximum current carrying capability, thereby preventing a fi re.

In a residential or commercial

electrical installation, the NEC requires both overcurrent protection and a disconnect switch. If

a circuit breaker is used as the overcurrent protection device, it can also be used as the required

DC disconnect.
If a fuse is used as an overcurrent device,

a C

lass-T type or equivalent is

recommended

. This fuse

type is rated for DC operation, can

handle the high short-circuit currents and

allow for momentary

current surges from the inverter without opening. However, because the fuse can be energized

from both directions, if it is accessible to unqualifi ed persons, the NEC requires that it be installed

in a manner that the power can be disconnected on both ends of the fuse before servicing.
See Table 2-3 to select the DC overcurrent device needed based on the minimum wire size ac-

cording to your inverter model.

Table 2-3, Recommended DC Wire/Overcurrent Device for Rated Use

Inverter

Model

Maximum

Continuous

Current

1

NEC

Current

2

Minimum DC

Wire Size

3

(conduit rating)

Maximum DC

Overcurrent

Device

4

DC Grounding

Electrode

Wire Size

5

MS4024AE

222 amps

278 amps

#2/0 AWG x 2

(312 amps)

300 amps

#6 AWG

MS4448AE

122 amps

153 amps

#2/0 AWG

(195 amps)

175 amps

#6 AWG

Installation

12345

Note 1 - Maximum Continuous Current is based on continuous power rating at the lowest input voltage.
Note 2 - NEC Current is based on the Maximum Continuous Current rating with a 125% NEC de-rating for

sizing the overcurrent device (when not continuous duty) to prevent it from being operated at more than

80% of rating.
Note 3 - Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F), with a

multiple cable fi ll factor (0.8) de-rating (if needed).
Note 4 - The next larger standard size overcurrent device may be used if the derated cable ampacity falls

between the standard overcurrent device sizes found in the NEC.

Note 5 - Per the NEC, the DC grounding electrode conductor can be a #6 AWG conductor if that is the only

connection to the grounding electrode and that grounding electrode is a rod, pipe, or plate electrode.