Maintenance/Troubleshooting
Page 48
Operating Instructions for Powador 3200-6600_EN
Authorised electrician
Status
Display
!
Explanation
Action
By
FS 58
Overtempera-
ture
Control card
The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.
"
Provide for suffi-
cient ventilation.
E
FS 59
Self test error
An error occurred during the buffer
inspection.
"
Notify your
authorised elec-
trician.
E
OS 60
Waiting for PV
voltage <550V
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specified value.
-
-
OS 61
External
limit (%)
The external „Power Control“ limit was
activated by the grid operator. The
inverter limits its power.
-
-
OS 62
Standalone
mode
PAC ####W
(###%)
The inverter was switched to islanding
operation by the Powador Grid-Save.
The inverter is disconnected from the
public low-voltage grid. The power
indicator percentage refers to the maxi-
mum AC power.
-
-
OS 63
Measured values
P(f)/frequency-dependent power
reduction: Frequency-dependent power
reduction will be activated when the
BDEW (German Association of Energy
and Water Industries) Medium Voltage
Directive goes into effect. Power reduc-
tion starts at a frequency of 50.2 Hz.
-
-
OS 64
Measured values
Output current limiting: The AC current
is limited once the specified maximum
value has been reached.
-
-
FS 66
Voltage trans.
fault
Plausibility test of ADC test between
ARM and DSP has failed
"
In case of
repeated occur-
rence:
Notify your
authorised elec-
trician.
E
FS
Config. error
Invalid CRC
The checksum of the loaded config. file
does not match the checksum in the
EEPROM. This means that the EEPROM
data originate from a different config.
file.
"
Notify author-
ised electrician /
KACO Service
E/K
Table 7:
Operating status and fault messages on the display