Installing the inverter

Page 19

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

1

Fixings for mounting

4

Suspension bracket

2

Wall bracket

5

Safety catch

3

Screws for mounting

Securing the inverter
7. Secure the inverter with a second person and with both hands on the housing side and base plate, and move

to the mounting location. (See Bild 9 auf Seite 17)

8. Hang the inverter on the wall holder using the suspension brackets on the back of the housing.
9. Secure the inverter with safety catch. (See Bild 12 auf Seite 18)

»

The mounting of the inverter is complete. Continue with the installation.

7

Installing the inverter

DANGER

Lethal voltages are still present in the terminals and cables of the inverter even after the

inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may open and install the inverter.
The inverter must be mounted in a fixed position before being connected electrically.

Observe all safety regulations and current technical connection specifications of the responsible

power supply company.

Disconnect the AC and DC sides.

Secure both sides against being inadvertently switched back on.

Ensure that the AC and DC sides are completely isolated and voltage free.

Connect the inverter only after the aforementioned steps have been taken.

7.1

Opening the connection area

Opening the connection area

↻ You have completed assembly.
1. Unscrew the two Philips screws on the right-hand side of the housing.
2. Open the housing door.

»

Make the electrical connection.

7.2

Making the electrical connection

Make the connection to the PV generator as well as the grid connection via the PCB terminals in the connection area

of the inverter. Note the following cable cross-sections:

AC connection DC connection

Max. conductor cross-section without wire sleeves

16 mm²

10 mm²

Max. conductor cross-section with wire sleeves

10 mm²

6 mm²

min. conductor cross-section for protective conductor acc. to IEC

standard 62109

10 mm² Cu

Length of insulation to be stripped off

10 mm

15 mm

Tightening torque

4-4.5 Nm

-