Configuration and Operation

Page 40

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Coun-

try-spec.

Settings

Menu

level

Display/

setting

Action in this menu/meaning

DE-NSP , BE

1

2

3

3

Reactive power

setting

The following control methods can be set. At least one

mode must be active.

- cos phi (P) : specific characteristic

- cos phi (P) : standard characteristic

- cos phi : x.xxx u (under excited) / o (over excited) (const)

- Q: xx.x % u (under excited) / o (over excited) (const)

- Q=f(U) standard characteristic

IT-CEI021

Additional

processes

"

Q=f(U) specific characteristic with 5 nodes

"

Q=f(U) specific characteristic with two-state control-

ler

IT-CEI021,

UD, IL

1

2

3

3

Q specification

active

"

Set the idle power Q (in % of device nominal power)

to a fixed value.

"

Select the type of phase shift (under-excited (u) /

over-excited (o)).

DE-NSP, BE,

IT-CEI021,

UD, IL

1

2

3

3

cos phi specification

active

"

Configure power factor.

"

If a power factor not equal to 1 is selected: Select the

type of phase shift (under-excited (u) /over-excited

(o)).

1

2

3

3

cos phi (P/Pn) active

The selection enables display, resetting or editing the

nodes. (min. 2 / max. 10)

"

Displays: All nodes are displayed in succession.

"

Reset: Press "1" to activate default characteristic and a

confirmation message is shown.

"

Edit: Specify the number of nodes for editing.

Increment P/Pn in % with key "2" and confirm with

key "1".

Increment cos phi with key "2" and confirm with

key "1".

NOTE: If a power factor not equal to 1 is selected: Select

the type of phase shift (under-excited/over-excited).
NOTE: After running through all selected nodes, all values

are saved by pressing "1" and this characteristic then is

checked for consistency.

NOTE: In the event of an error, the characteristic that was

previously active is restored and the error message "Char-

acteristic invalid" appears.

You then have the option of correcting the characteristic.

IT-CEI021

1

2

3

3

cos phi (P/Pn)

parameter?

Additional parameters can be set when cos phi (P/Pn)

function is active.

"

Specify gradient k. (Default value: 01000/1000)

"

Specify change time. (ms)

"

U_Lock In and U_Lock Out power range set as ‰ of

rated power, in which the network support process is

active.

DE, BE

1

2

3

3

Q(U) characteristic

"

Specify the target voltage.

"

Specify gradient.

"

Specify change time.