Configuration and Operation

Page 37

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Coun-

try-spec.

Settings

Menu

level

Display/

setting

Action in this menu/meaning

All countries

1

2

3

3

"Parameters" menu

Only service technicians are permitted to make changes

in the parameter menu.

↻ You are in menu level "1".

"

Press "2" for at least 15 seconds to open menu level 3.

1

2

3

3

Select country

The default setting is used if "no" is selected.

"

Set the desired country setting.

NOTE: This option influences the country-specific oper-

ating settings of the inverter. Please consult KACO service

for further information.

All countries

1

2

3

3

Set grid

parameters

"

Provides the option to set the grid parameters.

1. Confirm "Yes" input using "1" key.
2. Set the required grid parameters in the next menu.

"

If "No" is selected, the defined country-specific

parameters will be used.

ES, GB-G59

IT-CEI 021,

UD, IL

Undervoltage

shutdown

"

Specify the shutdown threshold

for fast and slow undervoltage shutdown.

"

Set period from occurrence of the fault to shutdown

of the inverter.

ES, GB-G59

IT-CEI 021,

UD, IL

Overvoltage

shutdown

"

Specify the shutdown threshold

for fast and slow overvoltage shutdown.

"

Set period from occurrence of the fault to shutdown

of the inverter.

DE-NSP,BE

"

Activate or deactivate password protection.

"

Specify the shutdown threshold

for overvoltage shutdown.

The 10-minute average for the measured voltage as

per EN50160 is used.

"

Set period from occurrence of the fault to shutdown

of the inverter.

AT, BG, CZ, FR

(not HTA), PF,

DE-VDN

Max. line voltage

EN 50160

The grid voltage is averaged over ten minutes. If the

defined value is exceeded, the inverter is disconnected

from the grid.

"

Set voltage threshold.

Voltage drop

between meter and

inverter

The voltage drop between the inverter and the grid-feed

meter is added to the limit value that was set for grid

shutdown according to EN 50160. The limit value can be

set from 0 to 11 V in 1 V increments.

"

Specify the switch-off value for the voltage drop (0 to

11 V).