EN

Maintenance/Troubleshooting

Page 45

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Fault

Cause of fault

Explanation/remedy

By

Additional devices

that are connected

via the poten-

tial-free contact

suddenly start up,

even though the

“priwatt” function is

deactivated and the

inverter indicates an

error.

The potential-free

contact connects

to indicate an

error.

If the “priwatt” function is not activated, the potential-free

contact functions as a fault signal relay and therefore indi-

cates errors. However, if additional devices that are provided

for the “priwatt” function are connected to the inverter via the

contact, they can still start up when the inverter experiences

an error, because the contact is connected at that point in

time. If you deactivate the “priwatt” function, we recommend

that you disconnect devices from the inverter that were con-

nected for this function.

Table 6:

Troubleshooting

9.5

Messages on the display and the "Fault" LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are

defined in standards, e. g. VDE0126-1-1. The inverter shuts down if the values exceed or fall below the approved levels.

9.5.1 Display of status and fault messages

Display

Fault LED (red)

FS (fault status)

!

ON

Fault signal relay has switched.

Feed-in was ended due to a fault.

OS (operating

status)

!

OFF

The fault signal relay releases again.

The inverter feeds back into the grid again after a coun-

try-specific time period.

Details regarding the fault or operating status can be found either on the display or in the data that was recorded

through the RS485 interface.

9.5.2 Status and fault signals

The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs. For

the status, consult the data that is logged via the RS485 interface.

BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.

Status

Display

!

Explanation

Action

By

OS 1

Waiting for

feed-in

Self-test: The grid parameters and gen-

erator voltage are being checked.

-

-

OS 2

Generator volt-

age

too low

Insufficient generator voltage and

power,

status before the transition to night

shutdown

-

-

OS 3

Constant volt. control
When feed-in begins, a constant gener-

ator voltage is fed in (80% of the meas-

ured open circuit voltage) for a short

period

Table 7:

Operating status and fault messages on the display