Maintenance/Troubleshooting

Page 46

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Status

Display

!

Explanation

Action

By

OS 4

MPP control
In cases of sufficient sunlight, the unit

feeds into the grid with MPP control so

as to maximise yields

OS 8

Self-test

Checks the shutdown of the power

electronics as well as the grid relay

before feed-in mode.

-

-

FS 10

Temperature in

unit too high

In case of overheating, the inverter

switches off. Possible causes:

Ambient temperature too high,

Fans covered,

Inverter defective.

"

Cool off the

area around the

inverter.

"

Uncover the

fans.

"

Notify your

authorised elec-

trician.

B

B

E

OS 11

Power limitation
Protective function of the inverter when

too much generator power is supplied

or the heat sink of the unit exceeds 75°C

FS 17

Powador Protect

shutdown

The activated grid and system protec-

tion has been tripped.

"

Notify your

authorised elec-

trician if the fault

occurs several

times.

E

OS 20

Active ramp lim-

itation

Internal power limiting
e.g.: "Ramp Up“ 10 %/Min

OS 29

Ground fault

Check fuse

A ground fault was detected on the DC

side.

"

Check the PV

generator

E

FS 30

Fault
Transformer fault

The current and voltage measurements

in the inverter are not within acceptable

range.

-

-

FS 32

Fault
Self-test

The internal grid separation relay test

has failed.

"

Notify your

authorised elec-

trician if the fault

occurs several

times.

E

FS 33

Fault
DC feed-in

The direct component of the line cur-

rent has exceeded the permitted value.

This DC feed-in can be caused by grid

conditions and may not necessarily

indicate a fault.

"

Notify your

authorised elec-

trician if the fault

occurs multiple

times.

E

FS 34

Communication

error

A communication error has occurred in

the internal data transmission.

"

Notify your

authorised elec-

trician.

E

FS 35

Protection shut-

down SW

Protective shutdown of the software

(AC overvoltage, AC overcurrent, DC link

overvoltage, DC overvoltage).

Not a fault

Grid-related

shutdown,

the grid connects

again automatically.

-

Table 7:

Operating status and fault messages on the display