Configuration and Operation

Page 38

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Coun-

try-spec.

Settings

Menu

level

Display/

setting

Action in this menu/meaning

AT

1

2

3

3

Undervoltage

shutdown

Displays the limit values for undervoltage or overvoltage

shutdown.

"

Define limit values for undervoltage or overvoltage

shutdown.

Overvoltage

shutdown

AU, DK,

GR-(M/I),

GB-G59, PT,

KR, SI

Line undervoltage/

overvoltage switch-

off

If the grid frequency exceeds or drops below the con-

figured values, the inverter switches off. The minimum

switch-off threshold can be set in 1 V increments.

"

Configure the switch-off values for undervoltage and

overvoltage.

ES, UD,

IT-CEI021,

GB-G59

Line underfre-

quency/

overfrequency shut-

down

The inverter continuously monitors the grid frequency.

If the grid frequency exceeds or drops below the config-

ured values, the inverter switches off.

"

Set limit values for fast and slow underfrequency

shutdown in 0.1 Hz increments

"

Enter the shutdown threshold for fast and slow over-

voltage shutdown.

AT, DE-NSP,

DE-VDN,

BE, AU, DK,

GR-(M/I), BG,

CZ, FR, PF, PT,

KR, SI

Under-/over-

frequency

shutdown

Shows the minimum/maximum allowable grid frequency.

"

Set limit values for underfrequency and overfre-

quency switch-off in 0.1 Hz increments

All countries

Minimum/

maximum

connection voltage

"

Set the shutdown threshold for the minimum and

maximum connection voltage:

NOTE: The limit values cannot be edited for DE-NSP,

DE-VDN and BE.

All countries

Minimum/

maximum

connection fre-

quency

Shows the minimum/maximum allowable grid frequency.

"

Set limit values for minimum and maximum connec-

tion frequency in 0.1 Hz increments.

NOTE: The limit values cannot be edited for DE-NSP,

DE-VDN and BE.

All countries

(not UD)

Three-phase

grid monitoring

Offers the option of activating three-phase grid monitor-

ing. During this process, single-phase grid monitoring is

deactivated.

"

Set grid monitoring.

DE-NSP, BE,

IL, UD

Connect time

"

Set connect time for grid monitoring after fault or

device start in 1 sec. increments.

All countries

(not GB)

Selection P(f)

Offers the option of regulating the active power depend-

ing on the frequency by two different processes.

"

Activate P(f) mode 1 or mode 2.

NOTE: For DE-NSP and BE, only Mode 2 is permitted.

For IT-CEI021 and DE-MSP is, only Mode 1 is permitted.

P(f) parameter for the countries/mains types shown in

bold cannot be edited.