EN

Maintenance/Troubleshooting

Page 47

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Status

Display

!

Explanation

Action

By

FS 36

Protection shut-

down HW

Protective shutdown of the

hardware (AC overvoltage, AC overcur-

rent, DC link overvoltage).

Not a fault

Grid-related

shutdown,

the grid connects

again automatically.

-

FS 38

Error

PV overvoltage

The voltage of the DC generator is too

high. The PV generator is configured

incorrectly.

"

Notify your

authorised elec-

trician.

E

FS 41

Line failure:
undervoltage L1

The voltage of a grid phase is too low;

the grid cannot be fed into. The phase

experiencing failure is displayed.

"

Notify your

authorised elec-

trician.

E

FS 42

Line failure:
overvoltage L1

The voltage of a grid phase is too high,

the grid cannot be fed into.

The phase experiencing failure is dis-

played.

"

Notify your

authorised elec-

trician.

E

FS 48

Line failure:
underfrequency

Grid frequency is too low.

This fault may be grid-related.

"

Notify your

authorised elec-

trician.

E

FS 49

Line failure:
overfrequency

Grid frequency is too high.

This fault may be grid-related.

"

Notify your

authorised elec-

trician.

E

FS 50

Line failure:
average voltage

The grid voltage measurement accord-

ing to EN 50160 has exceeded the maxi-

mum permitted limit value.

This fault may be grid-related.

"

Notify your

authorised elec-

trician.

E

FS 50

Line failure:
overvoltage L1

String voltage L1 is above the set maxi-

mum permissible string voltage

"

Notify your

authorised elec-

trician.

E

FS 51

Grid fault

(medium) over-

voltage L1

String voltage L1 is above the set maxi-

mum permissible string voltage

"

Notify your

authorised elec-

trician.

E

FS 52

Grid fault

(medium) over-

voltage L1

String voltage L1 is below the set mini-

mum permissible string voltage

"

Notify your

authorised elec-

trician.

E

FS 53

Grid fault

(medium) over-

voltage L2

String voltage L2 is above the set maxi-

mum permissible string voltage

"

Notify your

authorised elec-

trician.

E

FS 54

Grid fault

(medium) over-

voltage L2

String voltage L2 is below the set mini-

mum permissible string voltage

"

Notify your

authorised elec-

trician.

E

FS 55

Fault
DC link

Voltage at the DC link is too high, or

the DC link cannot be charged (IGBT

damage).

"

Notify your

authorised elec-

trician.

E

FS 56

Shutdown via digital input

Remote control for Italy CEI 0-21

Remote Trip-off

"

Notify your

authorised elec-

trician.

E

FS 57

Waiting for

reconnect

Waiting time of the inverter after a fault. Inverter does not

switch on again until

a country-specific

time has elapsed.

Table 7:

Operating status and fault messages on the display