Figure 4.15, Refer to, Table 4.10 – Yaskawa CIMR-PUxA User Manual

Page 98: For descriptions of ez sleep/wake-up parameters, 6 basic drive setup adjustments

background image

Wake-up

Level

reached

Wake-up

Timer

expired

Sleep

Level

reached

Sleep
Timer

expired

Wake-up

Level

reached

Wake-up

Timer

expired

Wake-up

Level

reached

Wake-up

Level

reached

Above

Wake-up

Level

Above

Wake-up

Level

PID Set-point

Run Command

Output Frequency

Wake-up Level <1>

Minimum Speed

(B5-91)

PID Feedback

EZ Sleep Level

(B5-92)

<1> Determined by EZ Wake-up Level (B5-94) and EZ Wake-up Mode (B5-95)

b5-96

b5-93

b5-96

b5-96

b5-96

Sleeping

Figure 4.15 EZ Sleep/Wake-up with Reverse Acting PID and b5-92 > b5-91

Table 4.10 EZ Sleep/Wake-up Parameters

No.

Name

Description

Values

b5-20

PID Setpoint Scaling

0: 0.01 Hz units

1: 0.01% units (100% = max output frequency)

2: RPM (number of motor poles must entered)

3: User-set (set scaling to b5-38 and b5-39, units based on b5-46 setting)

Default: 1

Range: 0 to 3

b5-38

PID Setpoint User Display

Scales the PID units to the maximum output frequency.

Default: 1000

Min.: 1

Max.: 60000

b5-46

PID Units Selection

Sets the display units for parameter b5-19, and monitors U5-01, U5-04 and U5-99

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (Inches of Mercury)

25: None

Default: 0

Range: 0 to 15; 25

b5-39

PID Setpoint Display Digits

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 2

Range: 0 to 3

b5-89

Sleep Method Selection

Determines how the drive sleeps and wakes-up when using PID.

0: Standard

1: EZ Sleep/Wake-up

Default: 0

Range: 0, 1

b5-90

<1>

EZ Sleep Unit

Sets the unit, range, and resolution of parameters b5-91 and b5-92.

0: Hz

1: RPM (number of motor poles must be entered)

Default: 0

Range: 0, 1

b5-91

<1>

EZ Minimum Speed

Sets the PID minimum speed and integral lower limit.

The internal value is lower limited to the higher setting between b5-34 and d2-02.

Default: 0.0 Hz

Range: 0.0 to

400.0 Hz
or 0 to 24000 RPM

<2>

4.6 Basic Drive Setup Adjustments

98

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide