beautypg.com

Yaskawa CIMR-PUxA User Manual

Page 132

background image

No.

Name

Setting Range

Default

L5-04

Fault Reset Interval Time

0.5 to 600.0 s

10.0 s

n

o1-06: User Monitor Selection Mode

Select between standard sequential monitors or selectable monitors to be displayed on the 2nd and 3rd lines of the digital

operator display.
Use parameters o1-07 and o1-08 to select and fix the second and third monitors shown in the Home (Frequency Reference)

and Monitor screen to ensure that those monitors are always visible when scrolling through the monitor list.

No.

Name

Setting Range

Default

o1-06

User Monitor Selection Mode

0, 1

0

Setting 0: 3 Mon Sequential (displays the next 2 sequential monitors)
Setting 1: 3 Mon Selectable (set by o1-07 and o1-08)

n

o1-07: Second Line User Monitor Selection

Selects the monitor that is shown in the second line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set “403” to display

monitor parameter U4-03.

No.

Name

Setting Range

Default

o1-07

Second Line User Monitor Selection

101 to 799

102

n

o1-08: Third Line User Monitor Selection

Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set “403” to display

monitor parameter U4-03.

No.

Name

Setting Range

Default

o1-08

Second Line User Monitor Selection

101 to 799

103

4.12 Fan and Pump Application Preset Details

132

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide