Yaskawa CIMR-PUxA User Manual

Page 131

background image

No.

Name

Setting Range

Default

L2-01

Momentary Power Loss Operation Selection

0 to 5

2

Setting 0: Disabled

If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.

Setting 1: Recover within L2-02

When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter

L2-02, the drive will perform Speed Search and attempt to resume operation. If power is not restored within this time (i.e.,

DC bus voltage level remains below Uv1 detection level L2-05), then a Uv1 fault is triggered and the drive will stop.

Setting 2: Recover as long as CPU Has Power

When a momentary power loss occurs, the drive output will be shut off. If the power returns and the drive control circuit has

power, the drive will attempt to perform Speed Search and resume the operation. This will not trigger a Uv1 fault.

Setting 3: Kinetic Energy Backup (KEB) Ride-Thru Operation within L2-02

The drive decelerates using regenerative energy from the motor until the time set in L2-02 has expired. It then tries to accelerate

back to the frequency reference. If the power does not return within the time set to L2-02, it will trigger a Uv1 fault and the

drive output will shut off. The type of KEB operation is determined by the L2-29 setting.

Setting 4: KEB Ride-Thru as long as CPU Has Power

The drive decelerates using regenerative energy from the motor until the power returns and then restarts. If the motor comes

to a stop before the power returns, the drive loses control power and the drive output shuts off. A Uv1 fault is not triggered.

The type of KEB operation is determined by the L2-29 setting.

Setting 5: Ramp to Stop with KEB Deceleration

The drive ramps to stop using the regenerative energy from the motor. Even if the power is restored, the drive will continue

to decelerate until the motor comes to a complete stop. The type of KEB operation is determined by the L2-29 setting. If an

input terminal set for KEB 1 (H1-oo = 65, 66) is triggered while the drive is decelerating, it will accelerate back up to speed

when the input is released.

Notes on Settings 1 through 5

• “Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not

output at this time.

• A Momentary Power Loss Unit is available to allow for a longer momentary power loss ride through time in models

2A0004 to 2A0056 and 4A0002 to 4A0031. This option makes it possible to continue running the drive after up to two

seconds of power loss.

• When using a magnetic contactor between the motor and the drive, keep the magnetic contactor closed as long as the drive

performs KEB operation or attempts to restart with Speed Search.

• Keep the Run command active during KEB operation or the drive cannot accelerate back to the frequency reference when

the power returns.

• When L2-01 is set to 3, 4, or 5, KEB Ride-Thru will be executed as specified in L2-29.

n

L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,

the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter

reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.

No.

Name

Setting Range

Default

L5-01

Number of Auto Restart Attempts

0 to 10 Times

0 Times

n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

4.12 Fan and Pump Application Preset Details

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

131

4

Start-Up Programming & Operation