beautypg.com

Control circuit wiring, Control circuit terminal block functions, 7 control circuit wiring – Yaskawa CIMR-PUxA User Manual

Page 66

background image

3.7 Control Circuit Wiring

u

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S8), multi-function digital outputs

(M1 to M4), multi-function analog inputs (A1 to A3), and multi-function analog monitor output (FM, AM). The default setting

is listed next to each terminal in

Figure 3.1

on page

43

.

WARNING!

Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with

untested control circuits could result in death or serious injury.
WARNING!

Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter

A1-03 may change the I/O terminal function automatically from the factory setting.

Refer to Application Selection on page 90

. Failure to

comply may result in death or serious injury.

n

Input Terminals

Table 3.7

lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.

Table 3.7 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Multi-Function

Digital Inputs

S1

Multi-function input 1

(Closed: Forward run, Open: Stop)

• Photocoupler
• 24 Vdc, 8 mA

Refer to Sinking/Sourcing Mode for Digital Inputs on page

71

.

202

S2

Multi-function input 2

(Closed: Reverse run, Open: Stop)

S3

Multi-function input 3

(External fault, N.O.)

S4

Multi-function input 4

(Fault reset)

S5

Multi-function input 5

(Multi-step speed reference 1)

S6

Multi-function input 6

(Multi-step speed reference 2)

S7

Multi-function input 7

(Jog reference)

S8

Multi-function input 8

(Baseblock command (N.O.))

SC

Multi-function input common

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs, 150 mA max

NOTICE:

Do not jumper or short terminals SP and SN. Failure

to comply will damage the drive.

71

SN

Digital input power supply 0 V

24 V transducer power supply 0 V

71

Analog Inputs /

Pulse Train

Input

RP

Multi-function pulse train input

(Frequency reference)

• Input frequency range: 0 to 32 kHz
• Signal Duty Cycle: 30 to 70%
• High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
• Input impedance: 3 kΩ

93

209

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

92

24 V +24 Vdc transducer power supply for customer

use

150 mA maximum capacity

A1

Multi-function analog input 1

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-01.

92

110

A2

Multi-function analog input 2

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-09.

92

92

112

A3

Multi-function analog input 3

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-05.

92

AC

Frequency reference common

0 V

92

E (G) Ground for shielded lines and option cards

3.7 Control Circuit Wiring

66