5.4 Operator Programming Errors

u

Operator Programming Error Codes, Causes, and Possible Solutions

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an

inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not

trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to

Table 5.4

for the appropriate action. When

an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.

Table 5.4 oPE Codes, Causes, and Possible Solutions

Digital Operator Display

Error Name

oPE01

Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.

oPE03

Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01

to H1-08.

oPE04

Initialization Required, Term <–> Ctrl Chg

oPE05

Run Command/Frequency Reference Source Selection Error

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,

H3-10, or H3-06 and PID functions conflict.

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is

enabled (b5-01 = 1 to 4).

oPE10

V/f Data Setting Error
One of the following setting errors has occurred:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

oPE28

oPE28

Sequence Timer Error
One or more of the sequence timers is not set in the correct order.