Setting 2: MEMOBUS/Modbus Communications

This setting requires entering the Run command via serial communications by connecting the RS-485/422 serial

communication cable to control terminals R+, R-, S+, and S- on the removable terminal block.

Setting 3: Option Card

This setting requires entering the Run command via the communication option board by plugging a communication option

board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into

the communication system.

Note:

If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the digital

operator and the drive will not run.

n

b1-03: Stopping Method Selection

Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.

No.

Parameter Name

Setting Range

Default

b1-03

Stopping Method Selection

0 to 3

0

Setting 0: Ramp to Stop

When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the

active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,

or Short Circuit Braking.

Refer to b2-01: DC Injection Braking Start Frequency on page 96

for details.

Setting 1: Coast to Stop

When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to

stop. The stopping time is determined by the inertia and the friction in the driven system.

Drive output is shut off

Run

command

Output

frequency

Motor speed

ON

OFF

Figure 4.8 Coast to Stop

Note:

After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do

not enter Run command until it has come to a complete stop. Use DC Injection at Start (

Refer to b2: DC Injection Braking and Short

Circuit Braking on page 185

) or Speed Search (

Refer to b3: Speed Search on page 186

) to restart the motor before it has completely

stopped.

Setting 2: DC Injection Braking to Stop

When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time

(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC Injection Braking is set in

parameter b2-02 into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly

faster compared to Coast to Stop.