beautypg.com

Yaskawa CIMR-PUxA User Manual

Page 113

background image

n

H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias

H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias

Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at

100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor

is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The

output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and

H4-08.

Figure 4.25

illustrates how gain and bias settings work.

No.

Name

Setting Range

Default

H4-02

Multi-Function Analog Output Terminal FM Gain

-999.9 to 999.9%

100.0%

H4-03

Multi-Function Analog Output Terminal FM Bias

-999.9 to 999.9%

0.0%

H4-05

Multi-Function Analog Output Terminal AM Gain

-999.9 to 999.9%

50.0%

H4-06

Multi-Function Analog Output Terminal AM Bias

-999.9 to 999.9%

0.0%

Using Gain and Bias to Adjust Output Signal Level

The output signal is adjustable while the drive is stopped.

Terminal FM

1.

View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-01 will be output from terminal FM.

2.

Adjust H4-02 viewing the monitor connected to the terminal FM.

3.

View the value set to H4-03 on the digital operator; terminal FM will output a voltage equal to 0% of the parameter

being set in H4-01.

4.

Adjust H4-03 viewing the output signal on the terminal FM.

Terminal AM

1.

View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-04 will be output from terminal AM.

2.

Adjust H4-05 viewing the monitor connected to the terminal AM.

3.

View the value set to H4-06 on the digital operator; terminal AM will output a voltage equal to 0% of the parameter

being set in H4-04.

4.

Adjust H4-06 viewing the output signal on the terminal AM.

Output Voltage

Output Voltage

0 V

5 V

10 V

Gain 150%
Bias 0%

Gain = 150%
Bias = 0%

Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%

Gain 100%
Bias 0%

Gain 50%
Bias 0%

100%

Monitor Value

Monitor Value

0%

H4-07, 08 = 0

H4-07, 08 = 1

10 V

-10 V

100%

5 V

15 V

-5 V

-15 V

-100%

Figure 4.25 Analog Output Gain and Bias Setting Example 1 and 2

Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

113

4

Start-Up Programming & Operation