Yaskawa CIMR-PUxA User Manual
Page 248

Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
Machine No.
Die Jaw
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Input Fuse Installation
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
.
Table C.5 Factory Recommended AC Drive Branch Circuit Protection (Normal Duty)
Drive Model
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating Amps
<3>
Bussman Semi-
conductor Fuse
Rating (Fuse
Ampere)
<4>
200 V Class
2A0004
0.75
3.9
15
6.25
10
FWH-70B (70)
2A0006
1 - 1.5
7.3
15
12
20
FWH-70B (70)
2A0008
2
8.8
15
15
25
FWH-70B (70)
2A0010
3
10.8
20
17.5
30
FWH-70B (70)
2A0012
3
13.9
25
20
40
FWH-70B (70)
2A0018
5
18.5
35
30
50
FWH-90B (90)
2A0021
7.5
24
45
40
70
FWH-90B (90)
2A0030
10
37
60
60
110
FWH-100B (100)
2A0040
15
52
100
90
150
FWH-200B (200)
2A0056
20
68
125
110
200
FWH-200B (200)
2A0069
25
80
150
125
225
FWH-200B (200)
2A0081
30
96
175
150
275
FWH-300A (300)
2A0110
40
111
200
175
300
FWH-300A (300)
2A0138
50
136
250
225
400
FWH-350A (350)
2A0169
60
164
300
250
450
FWH-400A (400)
2A0211
75
200
400
350
600
FWH-400A (400)
2A0250
100
271
500
450
800
FWH-600A (600)
2A0312
125
324
600
500
800
FWH-700A (700)
2A0360
150
394
700
600
1000
<5>
FWH-800A (800)
2A0415
175
471
900
800
1400
<5>
FWH-1000A (1000)
400 V Class
4A0002
1
2.1
15
3.5
6
FWH-40B (40)
4A0004
2
4.3
15
7.5
12
FWH-50B (50)
4A0005
3
5.9
15
10
17.5
FWH-70B (70)
4A0007
3
8.1
15
12
20
FWH-70B (70)
4A0009
5
9.4
15
15
25
FWH-90B (90)
4A0011
7.5
14
25
20
40
FWH-90B (90)
4A0018
10
20
40
35
60
FWH-80B (80)
4A0023
15
24
45
40
70
FWH-100B (100)
C.2 UL and CSA Standards
248
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide