4.6 Basic Drive Setup Adjustments

This section explains the basic settings required for initial drive operation. Checking these basic parameter settings will help

to ensure a successful drive start-up.

Refer to Parameter List on page 183

for a complete listing of drive parameters if more

information is required for parameters not listed in this section.

n

A1-03: Initialize Parameters

Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the

setting for A1-03 automatically returns to 0.

No.

Parameter Name

Setting Range

Default

A1-03

Initialize Parameters

0, 1110, 2220, 3330, 5550,

8008, 8009, 8010, 8011

0

Setting 0: No Initialize
Setting 1110: User Initialize

Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to

“1: Set defaults”.

Note:

User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to

clear the user-defined default values.

Setting 2220: 2-Wire Initialization

Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.

Setting 3330: 3-Wire Initialization

Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse

respectively.

Refer to Setting 0: 3-Wire Sequence on page 108

for more information on digital input functions.

Notes on Parameter Initialization

The parameters shown in

Table 4.7

will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330.

Table 4.7 Parameters Not Changed by Drive Initialization

No.

Parameter Name

A1-00

Language Selection

E1-03

V/f Pattern Selection

F6-08

Communication Parameter Reset

L8-35

Installation Selection

o2-04

Drive/kVA Selection

Setting 5550: Terminal/Control Initialize

An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed

in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.

Setting 8008: Pump

Application Preset for pump applications.

Refer to Fan and Pump Application Presets on page 125

for a list of parameters

and default values for this Application Preset.

Setting 8009: Pump w/ PI

Application Preset for pump with PI applications.

Refer to Fan and Pump Application Presets on page 125

for a list of

parameters and default values for this Application Preset.

Setting 8010: Fan

Application Preset for fan applications.

Refer to Fan and Pump Application Presets on page 125

for a list of parameters and

default values for this Application Preset.

Setting 8011: Fan w/ PI

Application Preset for fan with PI applications.

Refer to Fan and Pump Application Presets on page 125

for a list of

parameters and default values for this Application Preset.

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

91

4

Start-Up Programming & Operation