Ez sleep/wake-up function, For details, B2-01: dc injection braking start frequency – Yaskawa CIMR-PUxA User Manual

Page 96: B3-01: speed search selection at start

background image

Min output

frequency

100%

(Max output

frequency)

Output frequency

when Stop command

was entered

Run wait time t

Active deceleration time

Min Baseblock Time (L2-03)

Figure 4.12 Run Wait Time Depending on Output Frequency

n

b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).

No.

Name

Setting Range

Default

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

0.5 Hz

V/f Control

Sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01, DC

Injection Braking is enabled for the time set in parameter b2-04.

Output

Frequency

Time

b2-04

DC Injection

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 4.13 DC Injection Braking at Stop for V/f

Note:

If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the

E1-09 value.

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

0

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search

is complete.

u

EZ Sleep/Wake-up Function

To enable EZ Sleep/Wake-up functionality on the drive, first set parameter b5-89 to 1. The default setting for b5-89 is 0, which

disables the EZ Sleep functionality and related parameters, except for parameter b5-91, EZ Sleep Minimum Speed.
Setting b5-89 to 1 disables the existing PID Sleep function (b5-15) and enables the EZ Sleep/Wake-up functionality.
EZ Sleep and Minimum Speed Units
Parameter b5-90, EZ Sleep Unit, determines the unit, range, and resolution of parameters b5-92 and b5-93. When set to Hz,

the range is 0.1 to 400.0 Hz. When set to RPM, the range is 0 to 24000 RPM. Changing b5-90 will NOT automatically re-

scale the values of b5-92 and b5-93.
Minimum Speed

4.6 Basic Drive Setup Adjustments

96

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide