beautypg.com

Yaskawa CIMR-PUxA User Manual

Page 136

background image

CPF03

Control Board Connection Error
Connection error between the control board and the drive

CPF06

EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution

There is an error in EEPROM control circuit

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

The power supply was switched off while

parameters were being saved to the drive

Reinitialize the drive (A1-03 = 2220, 3330).

Digital Operator Display

Fault Name

CPF07

Terminal Board Connection Error

CPF08

or

CPF20 or CPF21

Control Circuit Error

CPF22

Hybrid IC Failure

CPF23

Control Board Connection Error
Connection error between the control board and the drive

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).

CPF25

Terminal Board Not Connected

to
to

CPF26 to CPF35

CPF40 to CPF43

Control Circuit Error
CPU error

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

E5

MECHATROLINK Watchdog Timer Error
The watchdog timed out.

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the PLC

and F6-03 is set to a value other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External Fault (input terminal S6)
External fault at multi-function input terminal S6.

5.2 Fault Detection

136

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide