beautypg.com

Figure 4.17, E1-01: input voltage setting, 6 basic drive setup adjustments – Yaskawa CIMR-PUxA User Manual

Page 102

background image

d1-04

d1-05

d1-06

d1-07

d1-17

d1-12

d1-13

d1-14

d1-15

d1-16

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

FWD (REV) Run/Stop

Multi-step Speed Ref. 2

Multi-step Speed Ref. 3

Jog Reference

Time

Multi-step Speed Ref. 1

Multi-step Speed Ref. 4

Frequency

reference

d1-01

(A1)

d1-02

(A2)

d1-03

(A3)

Figure 4.17 Preset Reference Timing Diagram

n

E1-01: Input Voltage Setting

Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal

voltage of the AC power supply.

NOTICE:

Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the

protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.

No.

Parameter Name

Setting Range

Default

E1-01

Input Voltage Setting

155 to 255 V

<1>

230 V

<1>

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.

E1-01 Related Values

The input voltage setting determines the overvoltage and undervoltage detection levels, the operation levels of the braking

transistor, the KEB function, and the overvoltage suppression function.

Voltage Setting Value of

E1-01

ov Detection Level/Dynamic

Braking Transistor Detection

Level

<1>

(rr Detection Level)

(Approximate Values)

Uv Detection Level

(L2-05)

Desired DC Bus Voltage

during KEB (L2-11)

ov Suppression /

Stall Prevention Level

(L3-17)

200 V

Class

All settings

410 V / 394 V

190 V

260 V

375 V

400 V

Class

setting ≥ 400 V

820 V / 788 V

380 V

500 V

750 V

setting < 400 V

820 V / 788 V

350 V

460 V

750 V

600 V

Class

All settings

1178 V / 1132 V

475 V

635 V

930 V

<1> The braking transistor operation levels are valid for the drive internal braking transistor. When using a CDBR braking unit, refer to instruction

manual TOBPC72060000 or TOBPC72060001.

4.6 Basic Drive Setup Adjustments

102

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide