beautypg.com

Application selection, Refer to application selection on, 5 application selection – Yaskawa CIMR-PUxA User Manual

Page 90

background image

4.5 Application Selection

Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application

Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values

appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.

User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple

menus.

Note:

1. Application Presets can only be selected if all drive parameters are at their original default settings.
2. Entering a value to A1-03 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first

setting A1-03 to 2220 or 3330 to initialize the drive.

WARNING!

Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter

A1-03 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.

No.

Parameter Name

Settings

Default

A1-03

Initialize Parameters

0: No initialization (default)

1110: User Initialize (parameter values

must be stored using parameter o2-03)

2220: 2-Wire Initialize

3330: 3-Wire Initialize

5550: Terminal/Control Initialize
8008: Pump

<1>

8009: Pump w/ PI

<1>

8010: Fan

<1>

8011: Fan w/ PI

<1>

0

A1-06

Application Presets (monitor only)

0: Disabled

8: Pump

9: Pump w/ PI

10: Fan

11: Fan w/ PI

0

<1>

Refer to Fan and Pump Application Presets on page 125

for drive setup using A1-03 = 8008, 8009, 8010, or 8011.

4.5 Application Selection

90

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide