beautypg.com

Fan and pump application preset details, 12 fan and pump application preset details – Yaskawa CIMR-PUxA User Manual

Page 128

background image

4.12 Fan and Pump Application Preset Details

n

b1-04: Reverse Operation Selection

Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause

problems (e.g., air handling units, pumps, etc.).

No.

Parameter Name

Setting Range

Default

b1-04

Reverse Operation Selection

0, 1

0

Setting 0: Reverse operation enabled

Possible to operate the motor in both forward and reverse directions.

Setting 1: Reverse operation disabled

Drive disregards a Reverse run command or a negative frequency reference.

n

b5-12: PID Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

No.

Parameter Name

Setting Range

Default

b5-12

PID Feedback Loss Detection Selection

0 to 5

0

Setting 0: Digital Output Only

A digital output set for “PID feedback low” (H2-oo = 3E) will be triggered if the PID feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-oo = 3F) will be

triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a

fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output resets when the feedback

value leaves the loss detection range.

Setting 1: Feedback Loss Alarm

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low”

alarm will be displayed and a digital output set for “PID feedback low” (H2-oo = 3E) will be triggered. If the PID feedback

value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed

and a digital output set for “PID feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output

(H1-oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection

range.

Setting 2: Feedback Loss Fault

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low”

fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH

- Feedback High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the

motor.

Setting 3: Digital Output Only, even if PID Is Disabled by Digital Input

Same as b5-12 = 0. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

Setting 4: Feedback Loss Alarm, even if PID Is Disabled by Digital Input

Same as b5-12 = 1. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

Setting 5: Feedback Loss fault, even if PID Is Disabled by Digital Input

Same as b5-12 = 2. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

n

b5-19: PID Setpoint Value

Used as the PID setpoint if parameter b5-18 = 1.

No.

Name

Setting Range

Default

b5-19

PID Setpoint Value

0.00 to 100.00%

0.00%

4.12 Fan and Pump Application Preset Details

128

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide