Using the Pulse Train Output

The pulse train output terminal MP can supply power or be used with an external power supply.

NOTICE:

Connect peripheral devices in accordance with the specifications. Failure to comply may cause unexpected drive operation, and

can damage the drive or connected circuits.

n

Using Power from the Pulse Output Terminal (Source Mode)

The high voltage level of the pulse output terminal depends on the load impedance.

Load Impedance R

L

(kΩ)

Output Voltage V

MP

(V) (insulated)

1.5 kΩ

5 V

4 kΩ

8 V

10 kΩ

10 V

Note:

The load resistance needed in order to get a certain high level voltage V

MP

can be calculated by: R

L

= V

MP

• 2 / (12 – V

MP

)

MP

AC

V

MP

R

L

Load Impedance

Figure 3.32 Pulse Output Connection Using Internal Voltage Supply

n

Using External Power Supply (Sink Mode)

The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between 12

and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.

External Power Supply (V)

Load Impedance (kΩ)

12 to 15 Vdc ±10%

1.0 kΩ or higher

MP

AC

Load Impedance

Sink Current

External Power Supply

Figure 3.33 Pulse Output Connection Using External Voltage Supply

u

Terminals A1, A2, and A3 Input Signal Selection

Terminals A1, A2, and A3 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as

explained in

Table 3.13

. Set parameters H3-01, H3-05, and H3-09 accordingly as shown in

Table 3.14

.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

3.8 Control I/O Connections