V/f Pattern Settings (E1-03)

The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined

V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which

maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that

requires the user to create the pattern using parameters E1-04 through E1-10.

n

E1-03: V/f Pattern Selection

Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.

No.

Parameter Name

Setting Range

Default

E1-03

V/f Pattern Selection

0 to F

F

<1>

<1> Parameter is not reset to the default value when the drive is initialized using A1-03.

Setting a Predefined V/f Pattern (Setting 0 to E)

Choose the V/f pattern that best meets the application demands from

Table 4.14

. These settings are available only in

V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.

Note:

1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.

Table 4.14 Predefined V/f Patterns

Setting

Specification

Characteristic

Application

0

50 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

1

60 Hz

2

60 Hz (with 50 Hz base)

3

72 Hz (with 60 Hz base)

4

50 Hz, Variable torque 1

Variable torque

For fans, pumps, and other applications where the required

torque changes as a function of the speed.

5

50 Hz, Variable torque 2

6

60 Hz, Variable torque 1

7

60 Hz, Variable torque 2

8

50 Hz, mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, high starting torque

A

60 Hz, mid starting torque

B

60 Hz, high starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04

to E1-13 are the same as those of setting 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009

The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the

values by 2.875 for 600 V drives.

Table 4.15 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

9

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

103

4

Start-Up Programming & Operation