89

• Setting Frequency by Current Reference Input

Never input voltage reference to control circuit terminal FR
when DIP switch SW8 is switched to “I” side. Damage to the
inverter may result.

When setting frequency by inputting
current reference (4-20mA or 0-20mA)
from the control circuit terminal FR,
switch the DIP switch SW8 on the control
circuit board to “I” side.

SW8 is accessed by removing the
terminal cover.

SW8