beautypg.com

Standard specifications (400v class) – Yaskawa VS mini J7 Series User Manual

Page 18

background image

18

• Standard Specifications (400V Class)

Voltage Class

400V 3-phase

Model

CIMR-J7A!!!!

3-phase

40P2

40P4

40P7

41P5

42P2

43P7

Max. Applicable Motor Output HP (kW)*

0.25

(0.2)

0.5

(0.4)

1

(0.75)

2

(1.5)

3

(2.2)

5

(3.7)

Ou

tp

u

t

Ch

ar

act

e

ris

tic

s

Inverter Capacity (kVA)

0.9

1.4

2.6

3.7

4.2

6.5

Rated Output Current (A)

1.2

1.8

3.4

4.8

5.5

8.6

Max. Output Voltage (V)

3-phase, 380 to 460V (proportional to input voltage)

Max. Output

Frequency (Hz)

400 Hz (Programmable)

Po

we

r

Su

pp

ly

Rated Input Voltage

and Frequency

3-phase, 380 to 460V, 50/60Hz

Allowable Voltage

Fluctuation

-15 to +10%

Allowable Frequency

Fluctuation

±

5%

Co

nt

ro

l

C

h

a

rac

te

ri

st

ic

s

Control Method

Sine wave PWM (V/f control)

Frequency Control Range

0.1 to 400Hz

Frequency Accuracy

(Temperature Change)

Digital reference:

±

0.01%, 14 to 122

°

F (-10 to

+50

°

C)

Analog reference:

±

0.5%, 59 to 95

°

F (25

±

10

°

C)

Frequency Setting Resolution

Digital reference: 0.1Hz (less than 100Hz) / 1Hz
(100Hz or more)
Analog reference: 1 / 1000 of max. output frequency

Output Frequency

Resolution

0.01Hz

Overload Capacity

150% rated output current for one minute

Frequency Reference

Signal

0 to 10VDC (20k

), 4 to 20mA (250

), 0 to 20mA

(250

) Frequency setting volume (Selectable)

Accel/Decel Time

0.1 to 999 sec. (accel/decel time are independently
programmed)

Braking Torque

Short-term average deceleration torque†
0.2kW: 150%
0.75kW: 100%
2HP (1.5kW): 50%
3HP (2.2kW) or more: 20%
Continuous regenerative torque: Approx. 20%

V/f Characteristics

Possible to program any V / f pattern

*

Based on a standard 4-pole motor for max. applicable motor output.

Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest
possible deceleration time.