Coast to stop (n04=1)

Upon removal of the FWD (REV) run command, the motor starts coasting.

DC injection braking current (n52)
Sets DC injection braking current level in units of 1%. (Inverter rated
current=100%)

DC injection braking time at stop (n53)
Sets the DC injection braking time at stopping in units of 0.1 second. When the
setting of n53 is 0, DC injection braking is not performed but inverter output is shut
OFF at the timing of DC injection braking start.

When coast to a stop is selected as the stopping method selection (n04), DC injection
braking at stop does not operate.

Applying DC injection braking

* When frequency reference is changed during running.