31
57
0139H
Stall prevention (current
limit) during running
Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will
not operate.
160%
92
58
013AH
Frequency detection
level
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
0.0Hz
74
59
013BH
Overtorque detection
0: Overtorque detection disabled.
1: Detects only at speed agree, opera-
tion continues after detection.
2: Detects only at speed agree, output
is shut down after detection.
3: Detects during run, operation contin-
ued after detection.
4: Detects during run, output is shut
down after detection.
0
73
60
013CH
Overtorque detection
level
Setting unit: 1%
Setting range: 30 ~ 200%
160%
73
61
013DH
Overtorque detection
time
Setting unit: 0.1s
Setting range: 0.1 ~ 10.0s
0.1s
73
62
013EH
Memory selection of hold
output frequency
0: Hold output frequency is not stored.
1: Hold output frequency is stored.
0
86
63
013FH
Torque compensation
gain
Setting unit: 0.1
Setting range: 0.0 ~ 2.5
1.0
60
64
0140H
Motor rated slip
Setting unit: 0.1Hz
Setting range: 0.0 ~ 20.0Hz
(Note 2)
-
65
0141H
Motor no-load current
Setting unit: 1%
Setting range: 0 ~ 99%
(Note 2)
-
66
0142H
Slip compensation gain
Setting unit: 0.1
Setting range: 0.0 ~ 2.5
1.0
93
67
0143H
Slip compensation
primary delay time
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
2.0s
93
68
0144H
Timeover detection
selection
0: Timeover detection enabled. (Coast
to stop)
1: Timeover detection enabled.
(Deceleration stop by deceleration
time 1)
2: Timeover detection enabled.
(Deceleration stop by deceleration
time 2)
3: Timeover detection enabled.
(Operation continues, alarm displays)
4: Timeover detection disabled.
0
-
69
0145H
Setting unit selection of
communications
frequency reference/
frequency monitor
0: 0.1Hz / 1
1: 0.01Hz / 1
2: 100% / 30000
3: 0.1% / 1
0
-
No.
Register
No. for
Trans-
mission
Name
Initial
Setting
User
Setting
Ref.
Page