40

0128H

Multi-function output
selection

0: Fault
1: During run
2: Frequency agree
3: During zero speed
4: Frequency detection
(detection level or greater)
5: Frequency detection
(detection level or less)
6: During over torque detection
(N. O. contact output)
7: During over torque detection
(N. C. contact output)
8: Not used
9: Not used
10: Minor fault (during warning display)
11: During baseblock
12: Run mode
13: Inverter ready
14: During fault retry
15: During UV
16: During reverse run
17: During speed search
18: Data output through communication

1

87

41

0129H

Analog frequency
reference gain

Setting unit: 1%
Setting range: 0 - 255%

100%

67

42

012AH

Analog frequency
reference bias

Setting unit: 1%
Setting range: –99 ~ 99%

0%

67

43

012BH

Analog frequency
reference filter time
parameter

Setting unit: 0.01s
Setting range: 0.00 ~ 2.00s
(Note)
When 0.00s is set, there is no filter

0.10s

-

No.

Register

No. for

Trans-

mission

Name

Description

Initial

Setting

*User

Setting

Ref.

Page