beautypg.com

Selecting run/stop commands – Yaskawa VS mini J7 Series User Manual

Page 62

background image

62

• Selecting Run/Stop Commands

Refer to page 63 to select either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.

LOCAL Mode

When Lo (local mode) is displayed on the digital operator (when

is

illuminated), or when the LOCAL / REMOTE changeover function is set as a
multi-function input and the input terminal is turned ON, run operation is enabled

by the

or

of the digital operator. FWD/REV is selected by

illuminating

and using

or

key to select FWD or REV.

REMOTE mode

Select remote mode

The following two methods are used to select remote mode:

1. Select rE (remote mode) for

selection.

2. When the local / remote switching function is selected as multi-function

input selection, turn OFF the input terminal to select remote mode.

Select operation method by setting the parameter n02.
n02=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 96)

Example for using the multi-function input terminal as operation reference
(two-wire sequence) follows. For 3-wire sequencing, refer to page 85.

Operating (RUN /STOP commands) by communications
(When option card is installed)

Setting parameter n02 to 2 in REMOTE mode can give RUN / STOP commands by
communication (MEMOBUS). For details, refer to page 96.