62
• Selecting Run/Stop Commands
Refer to page 63 to select either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.
•
LOCAL Mode
When Lo (local mode) is displayed on the digital operator (when
is
illuminated), or when the LOCAL / REMOTE changeover function is set as a
multi-function input and the input terminal is turned ON, run operation is enabled
by the
or
of the digital operator. FWD/REV is selected by
illuminating
and using
or
key to select FWD or REV.
•
REMOTE mode
•
Select remote mode
The following two methods are used to select remote mode:
1. Select rE (remote mode) for
selection.
2. When the local / remote switching function is selected as multi-function
input selection, turn OFF the input terminal to select remote mode.
•
Select operation method by setting the parameter n02.
n02=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 96)
•
Example for using the multi-function input terminal as operation reference
(two-wire sequence) follows. For 3-wire sequencing, refer to page 85.
•
Operating (RUN /STOP commands) by communications
(When option card is installed)
Setting parameter n02 to 2 in REMOTE mode can give RUN / STOP commands by
communication (MEMOBUS). For details, refer to page 96.