Yaskawa VS mini J7 Series User Manual

Page 106

background image

106

Blinking

Warning

Fault contacts
do not change
state.

BB (External base block)
Baseblock command at multi-
function terminal is active.
The inverter output is shut
OFF (motor coasting).
Temporary condition is
cleared when input command
is removed.

Check the external
circuit (sequence).

Blinking

EF (Simultaneous FWD/REV
run commands)
When FWD and REV run
commands are
simultaneously input for over
500ms, the inverter stops
according to parameter n04.

Check the external
circuit (sequence).

Blinking

STP (Operator function stop)
STOP/RESET is pressed
during running by the control
circuit terminals FWD/REV
command, or by the run
command from
communications. The inverter
stops according to parameter
n04.
STP (Emergency stop)
Inverter receives emergency
stop alarm signal. Inverter
stops according to parameter
n04.

Open FWD/REV
command of control
circuit terminals.

Check the external
circuit (sequence).

Blinking

FAN (Cooling fan fault)
Cooling fan is locked.

Check the following:
• Cooling fan
• Cooling fan wiring is

not connected.

Blinking

CE (MEMOBUS
communications fault)

Check the
communication devices
or communication
signals.

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN ALARM

(Green) (Red)

or