• Recommended Peripheral Devices

It is recommended that the following periheral devices be mounted between the AC
main circuit power supply and VS mini J7 input terminals R/L1, S/L2, and T/L3.

MCCB (Molded-case circuit breaker):

A circuit breaker should be connected for wiring protection.

Magnetic contactor:

Mount a surge suppressor on the coil (refer to the table shown below).

To assure optimum inverter life when using a magnetic contactor to start and stop
the inverter, do not exceed one stop per hour.

Recommended MCCB and magnetic contactor

200V 3-Phase

200V single-Phase

400V 3-Phase

VS mini J7 model

J7 * *

20P1

J7 * *
20P2

J7 * *
20P4

J7 * *
20P7

J7 * *
21P5

J7 * *
22P2

J7 * *
23P7

Capacity (kVA)

0.3

0.6

1.1

1.9

3.0

4.2

6.7

Rated Output Current (A)

0.8

1.6

3

5

8

11

17.5

MCCB type NF30
(MITSUBISHI)

5A

5A

5A

10A

20A

20A

30A

Magnetic contactor type HI
(YASKAWA CONTROL)

HI-7E

HI-7E

HI-7E

HI-7E

HI-10-2E

HI-10-2E

HI-20E

VS mini J7 model

J7 * *
B0P1

J7 * *
B0P2

J7 * *
B0P4

J7 * *
B0P7

J7 * *
B1P5

Capacity (kVA)

0.3

0.6

1.1

1.9

3.0

Rated Output Current (A)

0.8

1.6

3

5

8

MCCB type NF30, NF50
(MITSUBISHI)

5A

5A

10A

20A

20A

Magnetic contactor type HI
(YASKAWA CONTROL)

HI-7E

HI-7E

HI-7E

HI-10-2E

HI-15E

VS mini J7 model

J7 * *
40P1

J7 * *
40P2

J7**

40P4

J7 * *
41P5

J7 * *
42P2

J7 * *
43P7

Capacity (kVA)

0.9

1.4

2.6

3.7

4.2

7.0

Rated Output Current (A)

1.2

1.8

3.4

4.8

5.5

9.2

MCCB type NF30, NF50
(MITSUBISHI)

5A

5A

5A

10A

10A

20A

Magnetic contactor type HI
(YASKAWA CONTROL)

HI-7E

HI-7E

HI-7E

HI-10-2E

HI-10-2E

HI-10-2E