For display/clear of fault history, refer to page 29.

Protective
Operation

Output is shut
OFF and motor
coasts to a
stop.

CPF-05
AD converter fault is detected

Cycle power.
If the fault remains,
replace the inverter.

CPF-06
• Option card connecting

fault

• A non-corresponding option

card is connected.

Remove power to the
inverter.
Check the connection
of the digital operator.
Verify inverter software
number (n179).

CPF-07
Operator control circuit
(EEPROM or AD converter)
fault

Cycle power. If the fault
remains, replace the
digital operator or
inverter.

CE (MEMOBUS

communications fault)

Normal reception of
communication data is not
possible.

Check the
communication devices
or communication
signals.

Stops
according to
parameter.

STP (Emergency stop)
The inverter stops according
to parameter n04 after
receiving the emergency stop
fault signal.

Check the external
circuit (sequence).

(OFF)

• Insufficient power supply

voltage

• Control power supply fault
• Hardware fault

Check the following:
• Power supply

voltage.

• Main circuit power

supply wiring is
connected.

• Terminal screws are

securely tightened.

• Control sequence.
Replace the inverter.

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN ALARM

(Green) (Red)

or