• Parameters List

First Functions (Parameters n001 to n049)

No.

Register

No. for

Trans-

mission

Name

Description

Initial

Setting

*User

Setting

Ref.

Page

01

0101H

Parameter write-in
prohibit / initialize

0: Parameter n001 set / read and

parameter n02 ~ n79 can be read.

(FREF of the operator can be set.)

1: Functions (parameters n01 ~ n79)

can be set / read.

6: Clear fault history
8: 2 wire initialize
(Japanese Specification)
9: 3 wire initialize
(Japanese Specification)
10: 2 wire initialize
(American Specification)
11: 3 wire initialize
(American Specification)

1

57

02

0102H

Operation reference
selection

0: Operator
1: Control circuit terminal
2: Communication

1

62

03

0103H

Frequency reference
selection

0: Volume
1: Frequency reference 1 (n21)
2: Control circuit terminal
(voltage 0 ~ 10V)
3: Control circuit terminal
(current 4 - 20 mA)
4: Control circuit terminal
(current 0 - 20 mA)
5: Not used (setting error)
6: Communication
(register number 0002H)

2

63

04

0104H

Stopping method
selection

0: Decel to stop
1: Coast to stop

0

82

05

0105H

REV run prohibit

0: Reverse run enabled
1: Reverser run disabled

0

65

06

0106H

Operation stop key
selection

0: Stop key enabled
1: Stop key is enabled only when run
command is selected to the operator.

0

81

07

0107H

Frequency reference
selection
in local mode

0: Volume
1: Frequency reference selection (n21)

0 (Note4)

63

08

0108H

Setting method selection
for frequency reference

0: Frequency reference setting by the

operator is enabled with the ENTER
key input

1: Frequency reference setting by the

operator is not required the ENTER
key input.

0

63