• Setting Operation Conditions

The “Reverse run disabled” setting will not accept a reverse run command from the
control circuit terminal or digital operator. This setting is used for applications where a
reverse run command is undesirable.

Up to 8 preset references can be selected by using Multi-Function inputs.

Example: 8-step speed reference

Reverse run prohibit (n06)

Setting

Description

0

Reverse run enabled

1

Reverse run disabled

Multi-step speed selection

n02=1 (operation mode selection)

n03=1 (Frequency reference selection)

n21=25.0Hz (Frequency reference 1)

n22=30.0Hz (Frequency reference 2)

n23=35.0Hz (Frequency reference 3)

n24=40.0Hz (Frequency reference 4)

n25=45.0Hz (Frequency reference 5)

n26=50.0Hz (Frequency reference 6)

n27=55.0Hz (Frequency reference 7)

n28=60.0Hz (Frequency reference 8)

When all multi-function reference
inputs are OFF, frequency reference
selected by parameter n03
(frequency reference selection)

becomes effective.

n36=2 (Multi-function contact input terminal S2)

n37=6 (Multi-function contact input terminal S3)

n38=7 (Multi-function contact input terminal S4)

n39=8 (Multi-function contact input terminal S5)