• Setting Operation Conditions
The “Reverse run disabled” setting will not accept a reverse run command from the
control circuit terminal or digital operator. This setting is used for applications where a
reverse run command is undesirable.
Up to 8 preset references can be selected by using Multi-Function inputs.
Example: 8-step speed reference
Reverse run prohibit (n06)
Setting
Description
0
Reverse run enabled
1
Reverse run disabled
Multi-step speed selection
n02=1 (operation mode selection)
n03=1 (Frequency reference selection)
n21=25.0Hz (Frequency reference 1)
n22=30.0Hz (Frequency reference 2)
n23=35.0Hz (Frequency reference 3)
n24=40.0Hz (Frequency reference 4)
n25=45.0Hz (Frequency reference 5)
n26=50.0Hz (Frequency reference 6)
n27=55.0Hz (Frequency reference 7)
n28=60.0Hz (Frequency reference 8)
When all multi-function reference
inputs are OFF, frequency reference
selected by parameter n03
(frequency reference selection)
becomes effective.
n36=2 (Multi-function contact input terminal S2)
n37=6 (Multi-function contact input terminal S3)
n38=7 (Multi-function contact input terminal S4)
n39=8 (Multi-function contact input terminal S5)